450 meters east from the Shijialiancheng Village Committee in Shaozhuang Township, Suning County, Cangzhou City, Hebei Province, on the north side of the road
imgi_6_2
X
ZW32-40.5High Voltage Pole Mounted Vacuum Circuit Breaker Automatic/ Recloser With IEC Standard
ZW32-40 kV Series Intelligent Type Outdoor High Voltage AC Vacuum Circuit Breaker adopts an integrated solid sealing pole with unique design and a highly reliable operating mechanism. The device is mainly used in medium voltage overhead line power grid as load current, overload current and short-circuit current.High reliability.It is completely maintenance-free throughout its life.It has high mechanical life and electrical life.
Small volume and lightweight, easy to install.
Product Advantage
1. When considering the advantages of vacuum circuit breakers, it is important to note their superior features that set them apart from other types of circuit breakers. These advantages make vacuum circuit breakers a popular choice for various applications in the electrical industry.
2. One key advantage of vacuum circuit breakers is their high reliability. Due to the absence of any medium for arc extinction, vacuum circuit breakers are able to interrupt fault currents quickly and efficiently. This results in minimal downtime and increased operational efficiency.
3. Another advantage of vacuum circuit breakers is their compact design. With no need for bulky insulating materials, vacuum circuit breakers are more space-efficient and can be easily integrated into existing electrical systems.
4. Furthermore, vacuum circuit breakers are known for their long service life and low maintenance requirements. This makes them a cost-effective solution for both new installations and retrofit projects.
5. In addition, vacuum circuit breakers are environmentally friendly, as they do not use any harmful gases in their operation. This makes them a sustainable choice for environmentally conscious organizations.
6. Overall, the advantages of vacuum circuit breakers make them a reliable and efficient choice for a wide range of electrical applications.
Technical Parameters5.1 Circuit Breaker’s Main Technical Parameters Table
S/N
Name
Unit
Data Value
1
Rated Voltage
kV
40.5
2
Rated Current
A
1250/1600
3
Rated Frequency
Hz
50/60
4
1 min. Power Frequency Withstand Voltage (wet/dry)
kV
80 95/118
5
Lightning impulse Withstand Voltage (To earth/Fracture)
kV
185/215
6
Rated Short-circuit Breaking Current
kA
25/31.5
7
Rated Short-circuit Closing Current (Peak Value)
kA
63/80
8
Rated Short-time Withstand Current
kA
25/31.5
9
Rated Peak value Withstand Current
kA
63/80
10
Rated Short-time Continuous Time
s
5
11
Rated Operating Cycle
Times
0 – 0.3s – C0 – 180s – CO
12
Rated Short-circuit Current – Breaking Times
Times
30
13
Mechanical Life
Times
10000
14
Mechanism Control Voltage
V
AC/DC 220 AC/DC 110
15
Secondary Circuit 1 min Power Frequency Withstand Volt