    LW38-40 High Voltage Indoor SF6 Insulated Circuit Breaker For Switchgear And Substations

    Categories:

    Contact Now
    LW38-40.5w outdoor AC High-Voltage Sulfur Hexafluoride(SF6) circuit breaker (hereinafter referred to as “circuit breaker”) is an outdoor high-voltage distribution switchgear with three-phase AC 50Hz and rated voltage of 40.5kV. It can be used to open and close rated current and fault current, switch on and off capacitor banks, and switch lines. It is especially suitable for frequent operation and can also be used as a contact circuit breaker. The circuit breaker uses SF6 gas as the arc extinguishing and insulation quality is installed outdoors and adopts the elevated porcelain column structure. The circuit breaker complies with technical standards such as GB / t1984-2014 high voltage AC circuit breaker, DL / t402-2016 high voltage AC circuit breaker, and JB / T 9694-2008 high voltage AC sulfur fluoride circuit breaker. Product Advantage 1. SF6 vacuum circuit breaker has good electrical insulation properties, can maintain a low breakdown voltage under high voltage, safe and effective. 2. The high thermal conductivity of the gas absorbs the arc energy and cools down the arc very quickly, and cuts off the fault current rapidly. 3. The stability of the gas reduces the maintenance cost. 4. SF6 can work under harsh environmental conditions. 5. Compared with the traditional vacuum circuit breaker, SF6 vacuum circuit breaker is small in size, light in weight, compact in design, easy to install and maintain. Technical Parameters
    No. Item Unit Data
    1 Rated frequency Hz 50
    2 Rated voltage kV 40.5
    3 Rated current A 1250 / 1600 / 2000
    4 Rated Short-Circuit Breaking Current kA 31.5
    5 Rated Short-Circuit Closing Current 80
    6 Rated Short-Time Withstand Current 31.5
    7 Rated Peak Withstand Current 80
    8 Rated Out of Step Breaking Current 10
    9 Rated Short-Circuit Continuous Time s 4
    10 Rated Short-Circuit Breaking Current Breaking Times Times 10
    11 Rated short-time power frequency withstand voltage Interphase, to earth(dry) kV/min 95/1
    Fracture (dry) 118/1
    Interphase, to earth(wet) 80/1
    Auxiliary circuit to earth 2/1
    12 Rated lightning impulse withstand voltage Interphase, to earth kV 185
    Fracture 215
    13 Rated Operating Voltage and Auxiliary Circuit Rated Voltage V AC220, DC220
    14 Main Circuit Rsistance Rated Current 1600A and below micro-Ohm Not more than 90
    Rated Current more than 1600A Not more than 40
    15 Closing Time Under AC Voltage ms Not more than 100
    Under DC Voltage 55 ~ 100
    16 Opening Time Under AC Voltage Not more than 60
    Under DC Voltage 30 ~ 65
    17 Closing – Opening Time Not less than 120
    18 Opening – Closing Time Not more than 50
    19 Full Breaking Time Not more than 78
    20 Rated Operating Order O – 0.3s – CO -180s- CO
    21 Moving Contact Travel mm 96±2.5
    22 Contact Opening Distance mm 60±1.5
    23 Closing buffer Stroke mm 10±2
    24 Phase-to-Phase opening Synchronism ms Not more than 3
    25 Phase-to-Phase closing Synchronism ms Not more than 3
    26 Phase spacing mm 725
    27 Annual Gas Leakage rate of SF6 % Not more than 0.5
    28 SF6 Gas Moisture content (ppm, gauge pressure at 20 degrees Celcius) Handover Acceptance Value V/V Not more than 150
    Distance Travel Not more than 300
    29 SF6 Gas Rated Pressure (gauge pressure at 20oC) MPa 0.45
    30 SF6 Gas Replenish Pressure (gauge pressure at 20 oC) 0.42
    31 SF6 Gas Locked Pressure (gauge pressure at 20oC) 0.4
    32 Mechanical Life Times 6000
    33 SF6 Gas Weight Kg 5
    34 Weight (with CT) 800
    Weight (without CT) 1000
    Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate.
    USAGE USAGE: ENVIRONMENTAL CONDITION 1. Altitude: ≤ 1000m, If the altitude is higher than 1000m, the rated insulation level shall be corrected accordingly. 2. Ambient temperature: -40 oC ~ +45 oC, 3. Maximum daily temperature difference: 25 K 4. Humidity: Average daily relative humidity: 95%, average monthly relative humidity: 90%. 5. Sunshine intensity: not more than 0.1W/cm 2 6. Wind Speed: 34m/s 7. Wind pressure: 700Pa 8. Pollution level: e – level 9. Icing thickness: Not more than 10mm 10. Resistance to floor drain: horizontal acceleration 0.3g, vertical acceleration 0.2g Outline and Dimension

    Request Inquery